Reading the chart
Cover is measured from the top of the conduit or cable up to the finished grade, so the trench is deeper than the number by the height of the conduit and any bedding underneath. The most common residential answers: PVC conduit needs 18 inches in a yard, direct-burial UF cable needs 24 inches, and a 120-volt, 20-amp GFCI-protected circuit at a home can be 12 inches.
Under a home's driveway, PVC and UF need 18 inches. Under streets, roads, alleys and commercial driveways and parking lots, everything needs 24 inches.
Service lines follow the utility
The service line from the utility's transformer or pedestal to your meter is built to the utility's own specification, which is deeper than the NEC table. TEP and Trico each publish theirs, and the inspector or utility checks it. Underground service conductors buried 18 inches or more that are not in concrete also need a warning ribbon at least 12 inches above them. We dig service trenches to the utility's spec for your job; see electrical trenching.
Local rules and inspections
Each Arizona city and county adopts and amends the NEC on its own schedule. The City of Tucson enforces the 2023 NEC. Most jurisdictions want to see the trench open, with conduit in place, before it is backfilled, so schedule the inspection before the backfill crew comes back.
Backfill matters too: material with large rock or debris must not go where it can damage the conduit, which is why trenches through caliche get sand or screened bedding. The trench calculator works out how much.
Questions we get about this
How deep does PVC conduit need to be buried in a yard?
Eighteen inches of cover under NEC Table 300.5, measured from finished grade to the top of the conduit. That rises to 24 inches under streets, alleys and commercial parking, and stays at 18 inches under a one- or two-family home's driveway. Utility service conduit follows the utility's deeper specification.
Can I bury a GFCI circuit only 12 inches deep?
At a dwelling, a 120-volt branch circuit rated 20 amps or less with GFCI protection can have 12 inches of cover in most yard locations. It still needs 24 inches under roads and commercial parking. Confirm the circuit really meets all three conditions before you rely on the shallower depth.
How deep should conduit be under a driveway?
Under a one- or two-family home's driveway or parking area, PVC and rigid conduit need 18 inches and the GFCI branch circuit 12 inches. Under commercial driveways and parking lots, every wiring method needs 24 inches of cover.
Does Arizona have its own burial depth rule?
Arizona has no single statewide rule. Each city and county adopts the NEC, sometimes with amendments, and utilities set their own depths for service lines. The NEC table is the starting point; your jurisdiction and utility can require more.